Introduction to Ground Wire Standard
The grounding wire is a wire directly connected to the earth, which can also be called a safety loop wire. When it is dangerous, it transfers the high voltage directly to the earth, which is regarded as a lifeline.




The ground wire must not be connected to the neutral wire of the power supply, and the three-phase five-wire power supply shall not be shared with the lightning protection ground wire. The ground wire can be used as an anti-static ground wire (but the neutral wire and the ground wire shall not be mixed).
The cross-sectional area of the grounding trunk line should be no less than 100mm2, and the cross-sectional area of the branch trunk line should be no less than 6mm2; the grounding wire of the equipment and workbench should use multiple strands of plastic-coated wire with a cross-sectional area of 1.25mm2,
The color of the ground wire should be yellow-green wire, and the connection method of the main ground wire should be brazed.
The grounding wire connection terminal should ensure reliable contact, easy to install and disassemble, and allow the use of various clip-on connectors such as fish clips, plug sockets, etc.
The grounding wire should avoid sidewalks and building entrances and exits. The distance from the building should not be less than 1.5m, and the distance from the grounding body of the independent lightning rod should not be less than 3m. The upper end of the grounding wire should not be buried in depth less than 0.6m, and Should be buried in moist soil below the frozen ground
The grounding part of the equipment should be directly connected to the node trunk. There should be no less than 2 grounding wires, and the spacing should not be less than 2.5m. The grounding wire should be installed in a place that is convenient for inspection and does not hinder the disassembly of the equipment.